Airtightness
Testing
What you need to know?
This guide outlines the requirements of the approved Building
Regulations for 2006 as they apply to new dwellings. The
methodology of airtightness testing techniques is presented
along with diagnostic methods such as smoke testing and
thermographic surveys.
The 2002 Building Regulations required all commercial and
industrial buildings with a gross floor area greater than
1000 m2 to be tested for airtightness to a minimum standard
of 10 m3/(h.m2) at 50 Pascals (Pa). Not only does Approved
Document Part L2A of the Building Regulations for 2006 extend
this requirement to all sizes of commercial and industrial
buildings, Approved Document Part L1A is also extended to
include airtightness testing of new dwellings.
The Approved Document Part L1A for work in new dwellings
will require, with few exceptions, type-testing of all new
dwellings to an airtightness standard of no greater than
10 m3/(h.m2) at 50 Pa. For some dwellings where the carbon
emission rate is difficult to meet for architectural reasons,
then the airtightness target under the SAP calculations
may need to be reduced to 7, 5 or even 3 m3/(h.m2) at 50
Pa to meet the overall carbon emission rate required by
the Regulations.
Buildings containing rooms for residential purposes such
as nursing homes, student accommodation and similar are
not considered as dwellings. In such cases, Approved Document
Part L2A will apply.
Building contractors who elect to adopt the accredited details
route to demonstrating compliance with the Regulations will
still be required to undertake airtightness testing, albeit
with a potentially smaller sample of dwellings.

Who is this information aimed at?
Building Surveyors
To ensure new houses are sufficiently airtight, surveyors
will need to specify the appropriate forms of construction
as a matter of routine. By applying the BSRIA guidance,
building surveyors will help to reduce building failures
and save costs.
House Builders
The requirement for constructing low air-permeability dwellings
is here to stay, and are likely to become more arduous in
later editions of the Building Regulations. Housebuilders
will need to adopt quality assurance regimes to ensure that
air tightness testing becomes a routine task.
Testing Companies
The regulatory requirement to pressure test new dwellings
creates a need for airtightness testing companies with the
required level of calibrated equipment and personnel. In
addition to this guidance, BSRIA can provide all the help
organisations require in terms of training, equipment, and
instrument calibration.
Building Control
Building control officers will require test certificates
from qualified testing organisations in order to fulfil
their requirements under the Building Regulations. Testing
organisations will also need to demonstrate ongoing competency.

How do I comply with the Building Regulations?
Uncontrolled ventilation in dwellings through leakage paths
around doors and
window frames accounts for a significant proportion of heat
loss, particularly as
the insulation values of walls and glazing has improved.
In order to control this
energy loss, the Building Regulations will regulate the
overall leakage of the
building structure by testing, using a pressurising/depressurising
fan method.
This document specifically covers the methods used to comply
with the
airtightness component of the Regulations.
Air permeability
This is the same standard of air tightness as introduced
in Part L2 of the 2002
Building Regulations for buildings with a gross floor area
exceeding 1000 m2.
Essentially, it is the amount of air required to pressurise
and depressurise a
building to 50 Pascals (Pa), normalised with respect to
the building’s envelope area.
Envelope area is defined as the area of the external walls,
roof and footprint of
a building. A building’s footprint is usually defined
by the area of the ground
floor slab, except where the building has a basement. The
roof area is normally
defined as the area below the loft, where the loft is not
an accommodation
area (in other words not conditioned). The area of external
walls is only true
for detached properties. Semi-detached and terraced properties
will have partywall
elements.
Quality of Construction
While the maximum allowable building air leakage rate is
10 m3/(h.m2) at 50 Pa,
designers may choose to create an even more airtight construction
(7, 5 or even
3 m3/(h.m2) at 50 Pa) and to use the calculated energy saving
to trade off
against other building details. It is likely that detached
houses and bungalows
will have the greatest difficulty in meeting the Dwelling
carbon dioxide
Emission Rate (DER), and will require a tighter air permeability
specification.
The DER should be less than the Target carbon dioxide Emission
Rate (TER).
Where U-values for elemental type, allowable areas of windows
or doors, and
quoted efficiency of heating appliances do not (in total)
enable the dwelling to
meet the required TER, then the target air permeability
may need to be lower
than 10 m3/(h.m2) at 50 Pa.
Accredited and non-accredited construction
details
Both routes to airtightness compliance will require airtightness
testing of
samples of each dwelling type. For the purposes of Part
L1, a dwelling type
means a dwelling of the same generic form:
Detached,
semi-detached
End
terrace, mid-terrace
Mid-floor,
ground floor and top floor flats.
As different types of dwelling are not defined by their
floor area, the number
of bedrooms will not necessarily define a particular building
type. However,
different forms of wall or roof construction will be considered
to define a
dwelling type. Where a housing development has a mix of
construction forms,
it may require a higher number of air permeability tests.
The airtightness tests need to be carried out by an independent,
qualified (or
accredited) person in accordance with the procedures set
out in ATTMA
Technical Standard 1.
The pressure test value to be attained will be defined by
the designer in the
SAP 2005 evaluation, but in any case will not be greater
than 10 m3/(h.m2) as
this is the upper limit for air permeability set by the
Building Regulations,
except for developments with two or fewer dwellings. Registration
with the
British Institute of Non Destructive Testing (BINDT) with
respect to
airtightness testing would be a demonstration that the testing
organisation has
the appropriate skills.
Accredited Construction Details
On each development site, an air pressure test should be
carried out on a
unit of each dwelling type selected by the building control
body. A block of
flats should be treated as a separate development. On a
particular site, one of
each type of dwelling from the first completed batch of
units should be
tested to confirm the robustness of each design. A development
will not
usually comprise many different types of dwellings, often
less than ten.
However, achieving an air permeability of 10 m3/(h.m2) at
50 Pa should not
be an arduous task. This accredited construction detail
route to airtightness
testing will probably be preferred by most building contractors,
as it has the
potential to involve the fewest number of tests, although
it may prove far more
expensive than airtightness testing. As the building control
body will select the
dwellings to be tested, the builder must ensure that the
quality of
construction is consistent.
Non-Accredited Construction Details
Paragraph 58 of the draft Building Regulations says that
pre-completion pressure
testing will be required in accordance with the Table 1.
Table 1: The number of pressure tests for dwellings that
have not adopted accredited construction details (from table
3, paragraph 58, of Approved Document L1A Conservation of
Fuel and Power in New Dwellings).
| Number of instances of the dwelling
type |
Number
of tests to be carried out on the dwelling type |
| 4 or less |
One test of each dwelling type |
| Greater than 4 but equal to or less than 40 |
Two tests of each dwelling type |
| More than 40 |
At least 5% of the dwelling type,
unless the first five units of the type that are tested
achieve the design air permeability, when the sampling
frequency can be subsequently reduced to 2%. |
Sample size
With respect to sample size, 50% of the required airtightness
tests should be
carried out during construction of the first 25% of each
dwelling type.
This is simply to demonstrate to the building control officer
- as early as
possible in the building programme - that the buildings
are complying with
the Regulations.
It would be prudent (for best practice) to test the first
of each
dwelling type on each site in order to identify and modify
any details that are
causing an airtightness problem.
Consequences of failing a pressure
test
For the period up to 31 October 2007 the Regulations contain
what is called a
“reasonable provision in the event that initial test
results are unsatisfactory”.
This provision calls for remedial measures such that the
result of a re-test shows:
an improvement of 75% of the difference between the initial
test result and the target air permeability; or a test result
no worse than 15% greater than the target air permeability.
As was the case for large commercial and industrial buildings
in 2002, the
update to the Building Regulations for 2006 will include
an 18-month
introductory period whereby the target air permeability
will not be rigorously
applied.
For example, if the target value is set at 10 m3/(h.m2)
at 50 Pa, and the first test
result was 16 m3/(h.m2) at 50 Pa or less, then a repeat
test result of less than
11_5 m3/(h.m2) at 50 Pa will be deemed satisfactory. However,
if the result of
the first test resulted in a value greater than 16 m3/(h.m2)
at 50 Pa, the values
given in Table 2 would be required for the re-test.
Table 2: Pressure test failure and pass values.
| First test
(fail) m³/(h.m²) at 50 Pa |
Second
test (pass) m³/(h.m²) at 50 Pa |
| 18 |
<12 |
| 20 |
<12.5 |
| 22 |
<13 |
| 24 |
<13.5 |
Remedial measures
The Regulations stipulate that for each dwelling that fails
the initial test,
remedial measures should be carried out as required by paragraph
61, and one
further dwelling scheduled for testing.
It is a reporting requirement that the independent testing
company will know
the design target for the dwelling’s airtightness.
It is the responsibility of the
building control officer to ensure that all the appropriate
information relating
to the compliance of the Dwelling carbon dioxide Emission
Rate (DER)
fulfills the requirements of the Building Regulations. However,
in practice, it is
probable that the testing company will be in a position
to advise the client on
the need for remedial works and re-testing requirements.
All pressure tests will be undertaken early in the build
programme. If the
results are satisfactory to the extent that quality control
for later buildings on a
development site can be relaxed, this will help to reduce
the builder’s costs.
Exempted Areas
Note that where a conservatory is thermally separated from
the new dwelling
it will be regarded as an extension. Rules for extensions
are contained within
Part L1B which is for work in existing dwellings for which
no airtightness
testing is required. The situation for garages is a little
less clear, but if they are
not conditioned spaces, they would be outside the scope
of the Regulations.
|